Specimen for review. Print to A4 for the filed copy.

Tarnbeck Fire Door Services Ltd

Unit 4, Millrace Yard, Quarrendale ZZ99 9ZZ

020 7946 0127

office@example.com

Third-party certification: SAMPLE-0000

Fire door inspection report

Report number
TFD-2026-0418
Date of inspection
14 October 2026
Report issued
15 October 2026

Premises

Weaver's Court, 14 Fenwick Lane, Quarrendale ZZ99 9ZZ

Residential block, six storeys, 18 flats, one protected stair

Doors in scope: 6 (4 communal, 2 flat entrance)

Client

Quarrendale Homes (managing agent, for the responsible person)

Contact: Priya Nair, Property Manager

p.nair@example.com

07700 900362

Summary

6 doors inspected. 3 pass. 1 pass with advisory. 2 fail.

Two doors need remedial work before they can be relied on as fire doors (see Defects). Re-inspect on completion.

Next inspection due

Communal doors: 14 January 2027.

Flat entrance doors: 14 October 2027.

Failed doors: on completion of the remedial work listed.

Door schedule

Door IDLocationDoor typeResultNext dueNotes
FD-01Ground floor, entrance lobby to stairCommunal, single leaf, vision panelPass14 Jan 2027Closes onto latch from all test positions.
FD-02Ground floor, bin store to lobbyCommunal, single leafPass with advisory14 Jan 2027Signage faded on lobby face; replace at next visit.
FD-03First floor, stair lobby cross-corridorCommunal, single leaf, vision panelFailOn completion of remedial workHead strip missing; latch-side gap 6 mm. See defect D1.
FD-04Second floor, stair lobbyCommunal, single leafPass14 Jan 2027No action.
FD-05Flat 7, entrance doorFlat entrance, single leaf, letter plateFailOn completion of remedial workSelf-closing device does not close the door onto the latch. See defect D2.
FD-06Flat 12, entrance doorFlat entrance, single leaf, letter platePass14 Oct 2027No action.

Pass: meets every check. Pass with advisory: meets every check; one item will need attention before the next inspection. Fail: does not meet one or more checks; remedial action is required.

Fire door inspection report · Weaver's Court, 14 Fenwick Lane, Quarrendale ZZ99 9ZZ TFD-2026-0418 · Tarnbeck Fire Door Services Ltd

Checks applied to every door

Each door was checked against the items below. Items are written by Certledger from the responsible person's duties in England under the Regulatory Reform (Fire Safety) Order 2005, article 17, and the Fire Safety (England) Regulations 2022, regulation 10. Measurements and method reference BS 8214:2026.

No.CheckWhat a pass looks like
1Door leafNo holes, splits, warping or impact damage; no unauthorised alterations such as added vents, cables or cat flaps.
2Frame and fixingFrame secure to the wall on both sides and at the head; no gaps between frame and wall left unsealed.
3Gaps, head and sidesBetween 2 mm and 4 mm, measured at three points on each side and at the head.
4Gap at the thresholdWithin the limit for the door type and its seal; no daylight under a door fitted with a drop seal.
5Strips and sealsIntumescent strips and cold smoke seals present on every edge they are specified for, continuous, seated in their groove and undamaged.
6Self-closing deviceFitted and working: the door closes fully onto the latch from the fully open position and from a small opening, without being pushed.
7HingesThree hinges, all screws present and tight, no leaking oil, no visible wear or distortion; hinge marked for fire-door use.
8Latch and lockLatch engages and holds the door closed; any lock lets the door open from the inside without a key where the escape route requires it.
9GlazingGlass intact, no cracks; glazing beads secure; glass and beads of a type suitable for a fire door.
10Letter plate and ironmongeryLetter plate, spyhole and handles are types made for fire doors and are fitted in sound door material.
11Hold-open and wedgesNo wedge, hook or prop; any hold-open device releases when the fire alarm operates.
12Signage and identification"Fire door keep shut" or "Fire door keep locked" sign on the faces that need one; the door's identification label or plug is present and legible.
Fire door inspection report · Weaver's Court, 14 Fenwick Lane, Quarrendale ZZ99 9ZZ TFD-2026-0418 · Tarnbeck Fire Door Services Ltd

Defects and remedial actions

RefDoorDefect foundRemedial actionPriority
D1 FD-03, first floor stair lobby Intumescent strip missing from the head of the frame along its full length. Gap at the latch side 6 mm at mid-height, above the 4 mm limit. Fit a new intumescent strip to the head groove. Adjust or re-hang the leaf, or fit a lipping to the latch edge, to bring the gap to 2 to 4 mm. Re-inspect the door. Before the door is relied on; within 7 days
D2 FD-05, Flat 7 entrance Self-closing device stops the leaf 15 mm short of the latch from the small-opening test; door can be left unlatched. Adjust the closing and latching speed; if the device cannot be adjusted to close the door onto the latch, replace it with a device rated for the door. Re-inspect the door. Before the door is relied on; within 7 days

A1. FD-02: "Fire door keep shut" sign on the lobby face is faded. Replace before the next inspection.

Photographs of D1 and D2 were taken on site and are held on the Weaver's Court register.

Declaration

I inspected the doors listed in the door schedule on 14 October 2026, applying the checks listed on page 2 to each door. The results record the condition of each door at the time of inspection. A door marked fail does not meet one or more checks and the remedial action listed is needed before it can be relied on as a fire door. This report is not a fire risk assessment. It does not transfer the responsible person's duties in England under the Regulatory Reform (Fire Safety) Order 2005 or the Fire Safety (England) Regulations 2022, and it covers only the doors listed.

Inspected by Daniel Okafor, Fire Door Inspector, Tarnbeck Fire Door Services Ltd
Date 15 October 2026
Signed Daniel Okafor SPECIMEN

Received for the responsible person by: ______________________ Date: ____________